Buildings Energy Efficiency Ordinance, Data Centre Provisions
In force
Buildings Energy Efficiency Ordinance (Cap. 610), ss. 2, 7, 8, 21 and 22 and Schedules 1, 4, 5 and 6, as amended by Ordinance 24 of 2025
Effective 2026-09-20 · Applies to both
The Buildings Energy Efficiency Ordinance defines a data centre as a place for housing and operating computer systems, servers, telecommunications equipment and associated support components in a secure and controlled environment principally for providing data storage, data processing and data distribution services. A building occupied principally as a data centre, and a portion of an industrial building so occupied, are prescribed buildings in Schedule 1.
Part 2 of the Ordinance applies to such a building only where consent to the commencement of building works for superstructure construction is given after the relevant date. The developer must submit a stage one declaration within 2 months after that consent is given, and a developer who fails to do so is liable to a fine of $500,000 and a further $10,000 for each day the offence continues.
The owner of a building must cause an energy audit of its central building services installations at the intervals Schedule 5 specifies. Schedule 4 lists a building occupied principally as a data centre, and a portion of an industrial building so occupied. For a data centre in a portion of an industrial building that starts operation on or after the relevant date, the first energy audit is due 5 years after the date the data centre starts operation.
A data centre in such a portion that started operation before the relevant date must have its first energy audit within 1 year after the relevant date. A building occupied principally as a data centre takes its first energy audit on the timetable in Parts 3 and 5 of Schedule 6, and for both kinds of data centre each later energy audit is due within 5 years after the preceding one.
Part 4 does not apply to a building if the head of a Government department advises the Director in writing that an energy audit would be contrary to the interests of national security. The registered energy assessor sends the Director a Data Disclosure Form for publishing the technical information contained in the energy audit report. An owner of a building who contravenes the energy audit requirement commits an offence and is liable on conviction to a fine at level 5. The data centre provisions came into operation on 20 September 2026.
Source: Full text of law